摘 要

在当今社会,由于我国社会经济的不断发展,对电力系统的需求是越来越大,与此同时,对电力系统的技术要求也越来越苛刻,大容量、高压、超高压甚至特高压等级电网的不断出现,使得对于大电压、大电流的测量要求也在不断提高电力的安全运行比以往的任何时候都更加重要。与此同时传统的互感器类似动态范围小,绝缘性能差等问题层出不穷。于是在发展特高压电网及智能电网的背景下,新型电子式互感器的研究和应用深远影响着特高压电网和智能电网的发展。

这次,我的课题使用到的保护柜型号为深圳南瑞PRSC11-11,测控柜是国电南瑞出场的NSD500V,地刀和刀闸分别是CM102和CD101,断路器则是GL312型的。这次的二次回路的设计图纸将使用CAD软件绘制,并且还要同时完成一系列的整定计算(距离保护和零序保护)。

此次设计大致分为四个章节,首先的章节是引言,其次会写有关我这次设计的设备型号及参数和一些需要注意的情况,第三部分为110KV线路的距离三段保护和零序三段保护的整定计算,第四部分是关于这次设计的总结和展望,CAD图纸的绘制会做在附录中,这里就不在章节中列出了。

关键词 :整定计算;110kv线路保护;二次接线。

Abstract

In today"s society, due to the continuous development of social economy in our country, demand for power systems is getting bigger and bigger, and at the same time, the technical requirements of the power system are becoming more and more demanding., the safety and reliability of power supply in modern society have become increasingly demanding, large capacity, high pressure and ultra high pressure and high voltage power grid continue to emerge, making for high voltage, high current measurement requirements also in constantly improve the safe operation of power than any time in the past are more important. At the same time the traditional transformer similar dynamic range small, insulation, such as poor performance problems emerge in endlessly. So under the background of the development of UHV power grid and smart grid, the research and application of a new electronic transformer has a profound impact on the development of UHV power grid and smart grid.

This time, my project to use protection cabinet models for Shenzhen NARI PRSC11-11, the control cabinet is NSD500V Nari appearances, knife and knife switches are cm102 and CD101, the circuit breaker is GL312 type. The secondary circuit design drawings will use CAD software to draw, and must also complete a series of setting calculation of distance protection and zero sequence protection).

The design is divided into four chapters. The first chapter is the introduction, then write about the design of equipment models and the parameters and some need to pay attention to the situation. The third part for the three sections of 110kV transmission line distance protection and zero sequence protection setting calculation. The fourth part is the summary and Prospect about the design, CAD drawings drawing in the appendix, here is not in the chapters listed.

Key words: setting calculation; 110kV line protection; two connection.

目录

第一章 引言 1

第二章 关于设备的一些介绍 3

2.3 GL312 5

2.3.1 GL312的要求 5

2.3.2 分闸、合闸回路 5

2.3.4 自检闭锁、报警回路 6

第三章 11万伏线路整定计算 8

3.1整定任务 8

3.2.1一些基准值的选择 9

3.2.2 系统阻抗 9

3.2.3 有关参数 10

3.2.4输电线路的参数 11

第四章结论与展望 19

致 谢 20

参考文献 21

引言

通过简单的实验可以说明,电力系统一次回路设备在运行中不可避免的会受到损坏或者换一种说法回路自身也会因为这样那样的缺陷产生不必要的故障,以至引发事故。所以我们需要对这些回路中的装置进行有效的管理和监控,以及用于测量、控制信号等的二次电气设备的安全使用进行检测,这样就可以来预防或者说可以尽量避开可能发生的一些状况,通过这些说法,不难看出,二次设备对电力系统的意义重大,要是少了二次设备对电力系统的保护,电力系统可能会变得一团糟。

通过大量的实践证明关于二次设备对一次测的断路器等设备进行电压电流等量值的监测以及工作状态的控制、调节,发现该设备对一次侧有着保护的作用。而且这些二次设备会向正在监测的有关工作人员发送线路的运行状态或者还会向测试仪表以及继电保护装置等设备发送动作信号,使其正常运行,所以说由这些二次电气设备组成的电路就是我们说的二次回路一点都不夸张。